Fuel Storage Re-Circulation Kit

  • For fuel storage tanks up to 40,000/60,000L (3,000/5,000 litres per day).
  • Circulates & prevent degradation of fuel inside storage tanks.
  • Passes through a fuel conditioner to prevent microbial growth.
  • Fuel is automatically circulated for a preset number of timed periods to ensure tank contents is recirculated 11/2 times every 28 days.
  • When the pump flow rate drops below a preset limit (indicating a clogged filter) the flow switch closes & a warning light flashes.
  • Can link to our remote warning device
  • External alarm outputs, rated at 230VAC 10A max.
  • For use with Diesel/BioDiesel up to B30. (B100 version optional)
  • Features a 230V pump unit, inlet strainer, fuel conditioner, flow switch, filter clogged
  • warning light, timer & mains junction box.
  • Fitted on a wall/tank mounting plate.
  • Dimensions are 520mm H x 420mm W x 230mmD.
  • Complete unit is weatherproof.
Category: .